ELECTRICAL
RESISTANCE AND VOLTAGE DROP

The purpose of voltage in a circuit is to provide the required electrical energy to operate a load. Resistance and voltage drop across a load (such as a light bulb) are required for circuits to work correctly. But, in the wrong place (such as corrosion in a connector) resistance and voltage drop may causes electrical issues, such as dim bulbs, slow motors, heated wires, etc.

Resistance

A load can be defined as anything that causes resistance. This includes the wires and devices like switches, diodes, bulbs, or motors, etc. But, resistance can also be created by partial connectivity caused by loose terminal pins, pitted relay contacts, loose connections, or even corrosion. If a circuit has excessive resistance, it prevents the wire or component from carrying sufficient current under high load conditions. In a normally operating circuit, normal resistance is small enough that it doesn’t keep the load from operating properly.

Voltage Drop

When measuring voltage in a circuit, you’ll find that it is lower after the load (resistance) than it was before the load. The “voltage drop” or the amount that voltage lowers as it goes through a load is an indication or measure of how much electrical energy was used when it was converted into another form of energy (light, heat, or electromagnetic movement). The reason for using a voltage drop test rather than just an ohm meter to measure resistance, is that sometimes a resistance is not evident (not measureable) unless the circuit is placed under load.

Volts, Amps, and Resistance

When thinking of current in a circuit, sometimes it is helpful to visualize voltage as pressure and amperage as volume. One volt is the amount of electrical pressure needed to move one amp of current through one ohm of resistance.

Diagnostic First Steps

Resistance Test

Every part of an electrical circuit (wires, connectors, switch contacts, bulbs, motors, etc.) has some resistance. Most of the time we want that resistance to be very low, allowing for free flow of current through the circuit.

A multi-meter measures resistance in ohms. The ohmmeter function on a multii-meter is powered by an internal battery. It is used to apply a small voltage to a circuit or component and measure how much current flows through it, and then display the result as ohms of resistance.

Example of Measuring Test

Note: Before starting a test always check the ESM. Some vehicle circuits may have a resistor intentionally installed to reduce voltage and current. Examples include the rheostat that dims the instrument panel lights, ballast resistors in some fuel injector circuits, and motor resistors used to limit blower fan and electric fuel pump speeds. Be sure you know your circuit and identify any "intentional" resistance that can give high ohm reading or high voltage drop readings. Also, the ESM often has specifications for electrical testing.

Voltage Drop Test

Voltage drop testing provides a method for determining the amount of voltage that is being used by a wire or a component while the circuit is operating (under load).

When perfroming a voltage drop test as shown in this example; the volt meters positive lead should be connected to the circuit in the direction of the power source and negative lead toward the ground.

Operate or turn ON the circuit. Voltage will always follow the path of least resistance. So, if there is excessive resistance in the circuit, your meter becomes the path of least resistance for some voltage and will give a voltage reading.

NOTE: Voltage drop across a switch or relay should never exceed 0.3 volts (300mV). But less than 0.1 (100mV) is best.

In this example above;

  • There is a 0.1 voltage drop at the switch: 12.0 - 11.9 = 0.1 drop (OK)
  • There is a 4.0 voltage drop across the connection with high resistance: 11.9 - 7.9 = 4.0 drop (NG)
  • There is a 4.1 total voltage drop between the bettery and the light bulb. 12.0 - 7.9 = 4.1 drop (NG)
  • The measurement of 0 volts after the light bulb indicates that there is no resistance in the ground circuit. All the voltage in the circuit at that point is going directly back to the battery (path of least resistance) and no voltage is going through the meter (0 volt reading).
  • When testing circuits, you’ll often need to test the voltage at various points. A voltage drop can occur in any part of a circuit.

    Meter #1
    12 volts at the battery

    Meter #2
    0 volt reading between the battery positive post and the switch. The wire has no resistance so all of the voltage goes through the wire and none goes through the meter, giving a 0 volt reading - no voltage drop.

    Meter #3
    0.1 volt drop across the switch. The switch has a small resistance. 11.9 volts goes through the switch and the remaining voltage (0.1 volts) goes through the meter, giving a voltage drop reading of 0.1 volts.

    Meter #4
    4.0 volt drop across the damaged wire. The wire has high resistance at the fault point, allowing only 79 volts through the wire. The remaining 4 volts takes the path of least resistance through the meter giving a voltage drop reading of 4 volts. A voltage drop this high will likely cause problems, such as a dim bulb.

    Meter #5
    At this drop test location, we know that the 0.1 volt drop across the switch, and the damaged wire equal a voltage drop of 4.1 volts, leaving only 7.9 volts at the positive side of the bulb. This reading confirms that there is a 4.1 voltage drop in the circuit.

    Meter #6
    0 volt reading between the battery negative post and the bulb. The wire has no resistance so all of the voltage goes through the wire back to the battery. No voltage goes through the meter, giving a 0 volt reading - no voltage drop.

    Whenever a fault is suspected, both sides of the circuit should be tested. A complete circuit requires a source (positive side), load (light bulb, motor, etc), and ground (negative side). Always inspect both sides of the circuit. The ground side is often overlooked.

    Voltage Drops - Good or Bad?

    TIP: Is it Always Practical to Test Right at the Load? No, you may not always be able to have direct access to the load. For instance, you cannot connect your meter leads across the terminals of an in-tank fuel pump. You can only perfrom a voltage drop test on those parts of the circuit accessible to your meter leads.